Publication 1766-RM001A-EN-P - October 2008
436 Communications Instructions
In this example, the controller reads 10 elements from the target's N7 file,
starting at word N7:50 using 500CPU Read command. The 10 words are
placed in the controller's integer file starting at word N7:0. If 33 seconds
elapse before the message completes, error bit MG11:0/ER is set,
indicating that the message timed out.
If the target device is another MicroLogix 1400, a SLC 5/05, a PLC-5E or a
controller connected to Ethernet via a 1761-NET-ENI, then simply enter in
the device’s IP address in the “To Address” column as shown below under
the MultiHop tab.
For more information on routing through a ControlLogix gateway, refer to
Configuring a Multi-hop Remote Message on EtherNet/IP Communication
Channel on page 445.
efesotomasyon.com - Allen Bradley,Rockwell,plc,servo,drive