EasyManua.ls Logo

Allen-Bradley MicroLogix 1400 - Page 438

Allen-Bradley MicroLogix 1400
694 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Publication 1766-RM001A-EN-P - October 2008
436 Communications Instructions
In this example, the controller reads 10 elements from the target's N7 file,
starting at word N7:50 using 500CPU Read command. The 10 words are
placed in the controller's integer file starting at word N7:0. If 33 seconds
elapse before the message completes, error bit MG11:0/ER is set,
indicating that the message timed out.
If the target device is another MicroLogix 1400, a SLC 5/05, a PLC-5E or a
controller connected to Ethernet via a 1761-NET-ENI, then simply enter in
the device’s IP address in the “To Address” column as shown below under
the MultiHop tab.
For more information on routing through a ControlLogix gateway, refer to
Configuring a Multi-hop Remote Message on EtherNet/IP Communication
Channel on page 445.
efesotomasyon.com - Allen Bradley,Rockwell,plc,servo,drive

Table of Contents

Other manuals for Allen-Bradley MicroLogix 1400

Related product manuals