EasyManuals Logo

Allen-Bradley MicroLogix 1400 User Manual

Allen-Bradley MicroLogix 1400
694 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #502 background imageLoading...
Page #502 background image
Publication 1766-RM001A-EN-P - October 2008
500 Socket Interface Using CIP Generic Messaging
Read
The Read service reads data on a socket. You can specify a number of
bytes to receive. The Read service returns the number of bytes received.
For TCP, the Read service returns when any data is received, up to the
requested number of bytes. The Read service can return fewer bytes than
were requested. Your application might need to issue multiple Read
requests to receive an entire application message.
For UDP, the Read service completes when a datagram is available
MSG Configuration Parameters
To call this service, click "Setup Screen" in the MSG instruction and enter
the values displayed below.
Parameter Value
Service Type Read
Service Code 4D (hexadecimal)
Class 342 (hexadecimal)
Instance 0. Use a relay ladder instruction to move the returned
instance number from a CreateSocket service into the
MGx:y.TFN element of a MSG instruction
Attribute 0
efesotomasyon.com - Allen Bradley,Rockwell,plc,servo,drive

Table of Contents

Other manuals for Allen-Bradley MicroLogix 1400

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley MicroLogix 1400 and is the answer not in the manual?

Allen-Bradley MicroLogix 1400 Specifications

General IconGeneral
Processor32-bit
Expansion ModulesUp to 7 expansion I/O modules
Power Supply24V DC or 120/240V AC
Programming SoftwareRSLogix 500
Communication PortsEthernet, RS-232/RS-485 combo port
Controller TypeProgrammable Logic Controller (PLC)
SeriesMicroLogix
Digital Outputs12
Analog Inputs6 (embedded)
Analog Outputs2 (embedded)
High-Speed Counter6 high-speed counters
Pulse Output2 (embedded)
Ethernet PortYes

Related product manuals