Publication 1766-RM001A-EN-P - October 2008
610 Protocol Configuration
DF1 Radio Modem System Limitations
The following questions need to be answered in order to determine if you
can implement the new DF1 Radio Modem driver in your radio modem
network:
1. Do all of the devices support DF1 Radio Modem protocol?
In order to be configured with the DF1 Radio Modem driver, using
RSLogix 6.0 or higher, MicroLogix 1200 controllers must be at FRN 7
or higher and MicroLogix 1500 controllers must be at FRN 8 or
higher.
SLC 5/03, 5/04 or 5/05 processors must all be at FRN C/6 or higher
in order to be configured with the DF1 Radio Modem driver using
RSLogix 500/RSLogix Micro version 5.50 or higher.
All MicroLogix 1400 controllers support DF1 Radio Modem protocol.
RSLogix 500/RSLogix Micro version 7.0 or higher is required to
configure the MicroLogix 1400.
Starting with Version 16.1, all Logix controllers can be configured for
DF1 Radio Modem protocol.
2. Does each node receive the radio transmissions of every other node,
being both within radio transmission/reception range and on a
common receiving frequency (either via a “Simplex” radio mode or
via a single, common, full-duplex repeater)?
If so, then go to question #3 to see if you can use the DF1 Radio
Modem driver to set up a peer-to-peer radio network. If not, then
you may still be able to use the DF1 Radio Modem driver, by
configuring intermediary nodes as Store & Forward nodes.
3. Do the radio modems handle full-duplex data port buffering and
radio transmission collision avoidance?
If so, and the answer to #2 is yes as well, then you can take full
advantage of the peer-to-peer message initiation capability in every
node (i.e., the ladder logic in any node can trigger a MSG instruction
to any other node at any time). If not, then you may still be able to
use the DF1 Radio Modem driver, but only if you limit MSG
instruction initiation to a single “master” node whose transmission
can be received by every other node.
efesotomasyon.com - Allen Bradley,Rockwell,plc,servo,drive

Table of Contents

Other manuals for Allen-Bradley MicroLogix 1400

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley MicroLogix 1400 and is the answer not in the manual?

Allen-Bradley MicroLogix 1400 Specifications

General IconGeneral
Processor32-bit
Expansion ModulesUp to 7 expansion I/O modules
Power Supply24V DC or 120/240V AC
Programming SoftwareRSLogix 500
Communication PortsEthernet, RS-232/RS-485 combo port
Controller TypeProgrammable Logic Controller (PLC)
SeriesMicroLogix
Digital Outputs12
Analog Inputs6 (embedded)
Analog Outputs2 (embedded)
High-Speed Counter6 high-speed counters
Pulse Output2 (embedded)
Ethernet PortYes

Related product manuals