Rockwell Automation Publication 2711P-AP006C-EN-P - November 2018 15
Things to Know Before You Migrate Chapter 1
The PanelBuilder32 application performs additional steps that are not
required by the ME application.
4. Send Null (00) to the Data Tag, overwriting the alarm message.
5. Set the Notification Tag to 1.
6. Reset the Notification Tag to 0 when the Handshake tag changes to a
new nonzero value.
The Data tag is now ready to accept a new alarm message.
Tags Assigned to Message
Connections
Some PanelBuilder32 tags are assigned to Message connections in the
converted Machine Edition application.
This Tag in PanelBuilder32 Is Assigned to This Connection in ME
Remote Device Data tag Message connection
Remote Device Notification tag Message Notification connection
Remote Device Handshake tag Message Handshake connection