EasyManuals Logo

Ametek 3050-OLV User Manual

Ametek 3050-OLV
103 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #96 background imageLoading...
Page #96 background image
PN 305200901, Rev YT
Register #25 is a MODBUSCommand register. This register allows sending spe-
cial commands to the 3050 Analyzer as shown below.
Value Command Description
71 Start Verication
76 Load Sensor Memory
81 Quit Verication
82 Reset Analyzer
84 Start/Stop Test Mode
90 Start Zero Calibration
The last set of registers starting from #141 represents ASCII strings. Each reg-
ister is holding two ASCII characters. End of the string should be marked with
integer number of zero (‘’). For example, if the AnalyzerName variable is set to
“Dev, the holding register values are (considering that high byte located rst)
#141 (68, 101) and #142 (118, 0). Note that zero (‘’) indicates the end of the
ASCII string.
ID/Status Information
The Modbus master can poll the analyzer periodically for status information
via Modbus function 17 (11Hex). The returned information has the following
format:
1 byte Slave ID = 50h for 3050-OLV Analyzer
1 byte Run Status = FFh for Analyzer Online
(invalid signal = 0)
= 00h for Analyzer Oine
(invalid signal = 1)
2 bytes Status Word = System State which is Register 8
The most signicant byte comes rst.
15 bytes Model Name = Analyzer Model Name are Registers 213–220
12 bytes Serial Number = Analyzer Serial Number located in
Registers 183–189
4 bytes Version Number = S200 located in Register 82
The byte count is 35 (23Hex).
6-10 | 3050-OLV Moisture Analyzer

Table of Contents

Other manuals for Ametek 3050-OLV

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Ametek 3050-OLV and is the answer not in the manual?

Ametek 3050-OLV Specifications

General IconGeneral
BrandAmetek
Model3050-OLV
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals