User Manual – Rev BE    AMETEK Programmable Power 
MX Series  145 
4.2.11.2  VOLTAGE/CURRENT CONTROL SETUP menu 
 
Figure 4-23: VOLTAGE/CURRENT CONTROL SETUP Menu 
The VOLTAGE/CURRENT CONTROL SETUP menu may be used to set output 
voltage and current control parameters. These parameters are not frequently 
changed in the normal operation of the AC source and are thus located on the 
UTILITY rather than the PROGRAM menu. 
The following options are available in this menu: 
ALC MODE  Automatic Level Control of programmed output voltage. 
This mode will use the internal voltage measurements 
to adjust the output voltage continuously as needed. 
This effectively increases the output accuracy and 
regulation beyond what is possible with ALC off. 
  ON:  If ALC is ON, any event or load condition that 
prevents the power source from regulating the 
programmed voltage will cause it to trip the output off 
and generate a -801, “Output Voltage Fault”. There 
may be situations where it is desirable to continue 
driving the load even if the programmed voltage cannot 
be maintained. 
  REG:  In the REG (Regulate) mode ALC will regulate 
the output but not trip the output off if an event or 
condition prevents it from regulating.   
  OFF:  If the ALC is OFF, no additional regulation is 
performed by the controller other than the hardware 
control loop. 
  Note that if the current limit mode is set to CC 
(Constant Current) while the ALC is ON, the output will 
not trip off if the load current is at the programmed 
current limit forcing the unit into the CC operating 
mode, which requires the voltage to be reduced from 
the set value. 
NOTE:  The Automatic Voltage Level Control (ALC) mode is mutually 
exclusive with the Programmable Impedance function of the 
MX30-3Pi or MX45-3Pi. One must be turned off the enable the 
other.