January 2016 Page 3–33
Chapter 3. Applications
3
Figure 3–25b. FSK Mode, 2-Frequency, Unblock with STU Relay System - Settings
Module Function SoftwareSelection HardwareSelection Label Recommendation
Backplane CoaxSetting 2wire/4wire JMP3/JMP5 4wire
#ofPAs 1PA/2PA JMP2/JMP6 Perfactory
Coax
Impedance
50 W/75 W
JMP1/JMP4
50 W *
PowerSupply Power PwrOn/PwrOff JM P3 PwrOn
AlarmContact NO/NC JMP1/JMP2 PerEngineering
AuxPS JMP1/JMP2 46/20V
JMP3 20V
Input/Output
Input1 TripKey ApplicationofVoltage 15/48/125/250Vdc Input1 15V
Input2 PowerOff RemovalofVoltage 15/48/125/250Vdc Input2 PerEngineering
Input3 15/48/125/250Vdc Input3 PerEngineering
Input4 15/48/125/250Vdc Input4 PerEngineering
Input5 15/48/125/250Vdc Input5 PerEngineering
LL Output1 Guard 0.1/1.0 A LL01 PerEngineering
LL Output2 Trip NO 0.1/1.0 A LL02 0.1 A
LL Output3 GoodChannel NO 0.1/1.0 A LL03 0.1 A
LL Output4 Noise 0.1/1.0 A LL04 PerEngineering
LL Output5 RF Alarm 0.1/1.0 A LL05 PerEngineering
LL Output6 Checkback Trip NO 0.1/1.0 A LL06 0.1 A
LL Output7 0.1/1.0 A LL07 PerEngineering
LL Output8 NO/NC LL08 PerEngineering
LL Output9 NO/NC LL09 PerEngineering
LL Output10 General Alarm NO/NC LL10 PerEngineering
TDOutput1 Guard NO/NC TD01 PerEngineering
TDOutput2 Guard NO/NC TD02 PerEngineering
TDOutput3 Trip NO/NC TD03 PerEngineering
TDOutput4 Trip NO/NC TD04 PerEngineering
*Orperengineering’srecommendation
Programming / Jumper Table
Note: UPLC-II™ programmed for 2F-Unblock Standard
Configuration. If used opposite a TCF/TCF-10/TCF-10A, the trans-
mitter and receiver shift needs to be 100 Hz.