January 2016                                                                                                                   Page 5–23
Chapter 5. Installation/Commissioning Procedure
5
5.7.3 Input/Output Tab
5.7.3.1 Inputs (Fig. 5–10)
There are five inputs on the UPLC-II™. Each input
can  be set with a  contact  bounce  time  of  0–8 ms,
any of several selection choices, and if the input is
active for voltage applied or removed.
The input selection choice varies depending on the
channel  type  and  function  setting.  Table  5–12
shows the various input selection choices for differ-
ent channel type and function selections. Of course,
there is always  the  choice of “Not  Used.” You  do
not  have  to  program  all  inputs  just  the  ones  you
need.
Tables  5–13  &  5–14  show  the  definitions  of  the
inputs depending on whether the unit is in ON/OFF
or FSK mode.
There are 3 inputs that allow an external event to be
recorded as an SOE and time tagged by the UPLC-
II™.  The  inputs’  names  are  SOE Event  1,  2,  &  3
and they have the same SOE name in the sequence
of events file.
In FSK mode the (TX) Power Off input turns off the
transmitter so neither guard nor trip can be sent. It
is typically used for testing purposes. 
After you have  programmed  all the inputs  needed
click  on  the  “Continue”  button  and  you  will  be
taken to the Trip Duty Contact output programming
functions, if your UPLC-II™ has this option. If not
you will be taken to the Low Level output settings
page.  First  let’s  take  a  look  at  the  Trip  Duty
Outputs.
!
CAUTION
If  you  are  considering  setting  any  contact
bounce time please keep in mind that any time
other  than  0ms  will  affect  the  security  of  your
system.  If  any  time  is  set  and  you  get  a  very
short  input  of  100µs  or  less,  the  input  will  be
held for the total contact bounce time. It may be
wiser to let the input follow whatever is coming
in and let the receiver respond accordingly.