Page 3–26   
UPLC-II™ System Manual
3.6 Direct Transfer-Trip (DTT)
Systems
Direct transfer-trip systems provide circuit-break-
er tripping at remote or receiver terminals, without
any  supervision  by  fault  detectors.  The  most
important  consideration  in  a  direct  transfer-trip
system is the type  of  channel  applied. The  com-
munications  equipment  must  carry  the  total  bur-
den of system security and dependability.
Direct transfer-trip systems are applied for:
• Line protection with non-permissive under
reaching transfer-trip systems.
• Transformer  protection  where  there  is  no
circuit breaker between the transformer and
transmission line.
• Shunt reactor protection.
• Remote breaker failure protection.
A sample schematic is shown in figure 3-26, near
the end of the chapter.
3.6.1 Transformer Protection
A  typical transformer protection scheme  is  illus-
trated  in  Figure  3–17.  A  direct  trip  channel  is
keyed to the trip state when the transformer pro-
tective relays operate. The received trip signal will
then  trip  the  remote  end  breaker  and  lock  out
reclosing.
Although it is no longer widely used, you may use
a ground switch operated by the transformer pro-
tective  relays  for  transformer  protection.  In  this
technique, a ground fault is initiated on the trans-
mission  line  at  G,  providing  adequate
fault current for the ground relays at H to
trip the breaker at H. This system is slower but is
widely used on lower voltage systems and is fairly
simple and straightforward. It does not require any
secure communication medium between G and H.
For this type of application, the ground relays at H
can  be  set  to  operate  for  100 percent of the line
and not overreach to bus G.
While  a  single  switch  on  one  phase  is  normally
applied,  you  may  use  a  double  switch  on  two
phases to initiate a double-phase-to-ground fault.
In  the  latter  case,  both  phase  and  ground  relays
can operate to ensure redundancy. Fault grounding
is  not  applicable  to  all  systems  because  of  high
short-circuit capacity. 
3.6.2 Shunt Reactor Protection  
Shunt reactors  are  frequently  used  on  HV  and
EHV lines. These line reactors  are  connected on
the line side of the circuit breakers (Fig. 3–18). A
remote trip channel is thus required for a fault in
the shunt reactor.
3.6.3 Remote Breaker-Failure
Protection
A  remote  breaker-failure  system  is  necessary
where a multi-breaker bus, such as a breaker-and-
a-half or ring bus scheme, is applied at a transmis-
sion  line  terminal.  A  direct  transfer-trip  system
will be a part of the remote breaker-failure protec-
tion.
Direct Transfer Trip Channel
87
G H
Transformer Bank
Transmission Line
DTT
52c
52
TC
+
–
Figure 3–17. Direct Transfer Trip for Transformer Protection