EasyManuals Logo

Ametek UPLC-II User Manual

Ametek UPLC-II
200 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #112 background imageLoading...
Page #112 background image
Page 5–20
UPLC-II™ System Manual
Figure 5–8. Example of The Logic Tab on the Settings Page (ON/OFF Mode)
Figure 5–9. Example of The Logic Tab on the Settings Page (FSK Mode)
5.7.2 Logic Tab
See Fig. 5–8 (ON/OFF Mode) & 5–9 (FSK Mode). In the logic settings all the time selections are changed
in increments of 1 ms. The others are similar. See Chapter 2 for definitions of the various logic settings.
ON/OFF Directional Comparison & Phase Comparison Logic settings are shown in Table 5–6.
Caution should be taken when considering setting receiver dropout delay to anything other than 0
ms. Applying a setting of 1 15 ms can adversely affect relaying logic such as transient blocking
logic.
FSK Logic settings for the different functions are shown in Tables 57 through 511.
Note that GBT=Guard Before Trip.
When you have completed the logic settings click the “Continue” button.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Ametek UPLC-II and is the answer not in the manual?

Ametek UPLC-II Specifications

General IconGeneral
BrandAmetek
ModelUPLC-II
CategoryControl Unit
LanguageEnglish