Page 3–16   
UPLC-II™ System Manual
3.5 FSK Mode Protective Relay
Applications 
The UPLC-II™ carrier set is particularly suitable
for  the  following  types  of  protective  relay  sys-
tems:
• Directional Comparison Unblocking
• Permissive  Overreaching  Transfer  Trip
(POTT)
• Permissive  Underreaching  Transfer  Trip
(PUTT)
• Dual Phase Comparison Unblocking
• Segregated Phase Comparison Unblocking
• Direct Transfer Trip
3.5.1 Directional Comparison
Unblocking
The Directional Comparison Unblocking systems
transmit a continuous blocking signal, except dur-
ing  internal  faults.  The  channel  is  generally  a
Frequency-Shift  Keyed  (FSK)  Power-Line
Carrier. For an internal fault, the FSK transmitter
is shifted to the  “unblock”  frequency. The trans-
mitted power in many applications is normally 1
W, boosted to 10 W during unblock operation. 
The frequency-shift channel is monitored continu-
ously to  prevent tripping when a loss of channel
occurs.  The  carrier  receiver  logic  is  shown  in
Figure 3–8. Under normal conditions, a block fre-
quency  is  transmitted  and  OR-1  has  no  input.
Because AND-1 and AND-2 are not satisfied, OR-
2 is not energized. For an internal fault, the block
frequency is removed. Assuming that the unblock
signal is shorted out by the fault, OR-1 provides a
direct input to AND-2 to satisfy its input require-
ments for 150 ms. AND-2 inputs to OR-2 to oper-
ate the RR or to provide input to the AND shown
in Figure 3–8. Without an unblock signal, 150 ms
is allowed for tripping. After this period, lock out
is  initiated  as  one  of  the  inputs  to  AND-2  is
removed. This resets the RR or removes the input
to AND. If the unblock signal is received, it inputs
directly to OR-2 to energize the RR or to provide
input to AND. The unblock signal also removes an
input to AND-1 to stop the timer. A channel failure
(no  block  or  unblock  signal)  provides  input  to
AND-1  and,  after  150ms,  locks  out  the  relaying
and triggers an alarm. The operation of the scheme
shown  in  Figure 3–9  is  given  in  Table  3–4  for
external and internal faults. The phase and ground
trip  fault  detectors  at  both  stations  must  operate
for all internal faults; that is, they must overreach
the remote bus.
The  dependability  and  security  of  Directional
Comparison  Unblocking  systems  make  them  the
most attractive of the protective schemes for trans-
mission lines using Power-Line Carrier channels.
Over-tripping is  avoided  by  continuous  blocking
and  continuous  channel  monitoring.  Only  an
external  fault  within  a  certain  time  delay  after
channel  failure  can  result  in  over-tripping.  This
time is selectable from 0-500ms. 
The scheme is most appropriate for two-terminal
lines,  but  is  applicable  to  multi-terminal  lines.
Separate channels are required between each ter-
minal  and  the  remote  terminal(s).  A  sample
schematic is shown in Figure 3–23, near the end
of this chapter.
You may conserve frequency spectrum by using a
narrow  band  frequency  shift  carrier,  but  at  the
expense of channel speed. 
Another  consideration  is
an open breaker situation.
When  the remote breaker
is  open  for  an  extended
period  of  time,  the  relay
system  must  be  able  to
trip. The remote relay sys-
tem  sends  a  trip  signal
when  detecting  a  remote
Block
Frequency
Unblock(Trip)
Frequency
Lockout
(0=disabled)
ToRRor
AND
AND
2
AND
1
OR
2
0-500
ms
0
OR
1
Figure 3–8. Simplified Unblock Receiver Logic