Troubleshooting
160
NXD/T-1200V Wall/Flush Mount Touch Panel
Troubleshooting Information (Cont.)
Symptom Solution
There is a crawling, dashed line on
the left border of the graphics.
On some units at some resolutions, there are wavy lines across the entire
screen. This has been seen on middle resolutions and is referred to as the
"Mid Range Fallout" problem.
This is due to the graphics controller settings in the firmware.
Update firmware to the latest v2.XX. firmware.
Visit the www.amx.com > Tech Center > Downloadable Files > Firmware
Files > Modero panels. Then Download the KIT file to your computer.
My Modero panel isn’t appearing in
my Workspace window.
Verify that the System number is the same on both the NetLinx Workspace
window and the System Settings page on the Modero panel.
Verify you have entered the proper NetLinx Master IP and connection
methods into the Master Connection section of the System Settings page.
Refer to the System Settings Page section on page 102 for more
information.
My Modero panel can’t obtain a
DHCP Address
In requesting a DHCP Address, the DHCP Server can take up to a few minutes to
provide the address.
Verify there is an active Ethernet connection attached to the rear of the
Modero before beginning these procedures.
•Select Diagnostics > Network Address, from the Main menu and verify the
System number.
If the IP Address field is still empty, give the Modero a few minutes to
negotiate a DHCP Address and try again.
My NXT-BP battery pack is
blinking when I check the battery life
indicator.
A blinking battery life LED indicates that there is less than 10% power
charge remaining on the battery.
It is recommended that you fully charge the battery either in the
NXA-BASE/B battery base or in the NXT-CHG battery charger.
Refer to the NXA-BASE/B Battery Base Kit (FG2255K) section on page 22
for more information.
I was using the power from PSN, and
when I connected my
NXA-BASE/B battery base to the
active panel, my screen went blank.
Modero battery bases can not be "hot-swapped" or replaced without
powering down the Modero and removing the PSN connector.
If you are currently using a direct power connection to the panel and then wish
to connect an NXA-BASE/B.
First, power-down the panel and detach the rear power connection. Then,
remove any batteries from within the NXA-BASE/B and connect the battery
base to the underside of the panel.
After connecting the base to the un-powered panel, then run power to the panel
by either reconnecting the power cable to the rear of the panel or inserting the
NXT-BP batteries into the NXA-BASE/B.
Refer to the NXA-BASE/B Battery Base Kit (FG2255K) section on page 22
and Installing the NXA-BASE/B to an NXT Modero Panel section on page 23
for more information.
My WEP doesn’t seem to be
working.
WEP will not work unless the same default key is set on both the panel and
the AP.
For example: if you had your access point set to default key 4 which was
01:02:03:04:05 and you set the Modero to key 1 which was also
01:02:03:04:05 it will not work. You have to set key 4 on the Modero to
01:02:03:04:0.