9.3.6. EMERGENCY position
If the EMERGENCY operation Approach EMCY pos. is set, the actuator moves to
the EMERGENCY position entered here.
Required user level: Specialist (4) or higher.
Customer settings M0041
EMCY behaviour M0198
EMCY position M0232
Default value: 0.0 %
Setting range: 0.0 … 100.0 % (from end position OPEN to CLOSED)
9.3.7. EMERGENCY speed
Speed for an EMERGENCY operation.
Required user level: Specialist (4) or higher.
Customer settings M0041
EMCY behaviour M0198
Speed EMCY OPEN M1934
Speed EMCY CLOSE M2041
Default value: 6 (rpm)
Setting range: 6 ... 240 (rpm)
The adjustable speed range is indicated on the actuator name plate.
9.3.8. Torque switching: by-pass
If the EMERGENCY signal initiates an EMERGENCY operation, the torque switching
can be by-passed during this operation.
Required access level: Specialist (4) or higher.
Customer settings M0041
EMCY behaviour M0198
By-pass torque M0199
Default value: Off
Setting values:
Off
No by-pass of the torque switching.
On
The signals of the torque switching in the actuator are by-passed
9.3.9. Motor protection: by-pass
If the EMERGENCY signal initiates an EMERGENCY operation, the motor protection
can be by-passed during this operation.
Required user level: Specialist (4) or higher.
Customer settings M0041
EMCY behaviour M0198
Thermal by-pass M0200
Default value: Off
Setting values:
Off
No by-pass of motor protection.
On
The signals of the thermoswitches or the PTC thermistors of the motor winding are
by-passed.
Information
It is not possible to by-pass the motor protection for actuators with explosion protec-
tion.
78
Actuator controls
Failure functions ACV 01.2/ACVExC 01.2