9.
Enter password ( enter password).
Display shows the set value.
The bottom row indicates: EditEsc
10.
Press Edit.
Change value
11.
Enter new value for tripping torque via Up Down .
Information: The adjustable torque range is shown in round brackets.
12.
Save new value via Save.
The tripping torque is set.
13.
Back to step 4 (CLOSED or OPEN): Press Esc.
Information
The following fault signals are issued if the torque setting performed has been reached
in mid-travel:
In the display of the local controls: Status indication S0007 Fault
Torque fault OPEN or Torque fault CLOSE
The fault has to be acknowledged before the operation can be resumed. The
acknowledgement is made:
1. either by an operation command in the opposite direction.
-
For Torque fault OPEN : Operation command in direction CLOSE
-
For Torque fault CLOSE : Operation command in direction OPEN
2. or, in case the torque applied is lower than the preset tripping torque:
- in selector switch position Local control (LOCAL) via push button RESET.
- in selector switch position Remote control (REMOTE):
- via a digital (I/O interface) with the Reset command if a digital input
is configured for RESET signal.
7.3. Limit switching
Conditions
Electronic control unit with MWG in the actuator (non-intrusive version)
For an electro-mechanical control unit equipped with switches in the actuator (intrusive
version), the limit switches are set as described in the operation instructions.
Functions
Tripping in end positions (limit seating)
Signalling the end positions (torque seating)
7.3.1. Limit switching: set
Customer settings M0041
Limit switching M0010
Set end pos.CLOSED? M0084
Set end pos. OPEN? M0085
Select main menu
1. Set selector switch to position 0 (OFF).
2. Press push button C and hold it down for approx. 3 seconds.
Display goes to main menu and indicates: Display...
Select parameter
3. Select parameter either:
click via the menu to parameter, or
via direct display: press and enter ID M0084.
Display indicates: Set end pos.CLOSED?
39
Actuator controls
ACV 01.2/ACVExC 01.2 Basic settings for commissioning

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AUMA ACVExC 01.2 Series and is the answer not in the manual?

AUMA ACVExC 01.2 Series Specifications

General IconGeneral
BrandAUMA
ModelACVExC 01.2 Series
CategoryController
LanguageEnglish

Related product manuals