Function active
Function <Local controls: enable from REMOTE> activated.
9.4.2. Enabling function behaviour
The enable behaviour determines which selector switch functions (LOCAL, OFF)
require an additional enable signal.
Required user level: Specialist (4) or higher.
Customer settings M0041
Local controls M0075
Enable LOCAL M0628
Default value: Sel. sw. Local
Setting values:
Sel. sw. Local
Disabling or enabling is only effective in operation mode LOCAL (selector switch is
in position Local control). If no enable signal is present, operation via push buttons
on the local controls is disabled and the display shows the following signal:Disabled.
Sel. sw. Local + Off
Disabling or enabling is effective in operation modes LOCAL and OFF (selector
switch positions Local control and 0). If no enable signal is present, operation via
push buttons on the local controls is disabled and the display shows the following
signal: Disabled.
Information
If the <Priority REMOTE> function is also activated, the two functions should have
different setting values. In case of identical setting values, e.g. Sel. sw. Local + Off,
the <Enable local controls> function will have no function, since the actuator controls
will be exclusively in operation mode REMOTE if the enable signal is missing.
9.5. Priority REMOTE
Characteristics
A control signal can provide REMOTE control with priority over actuator operation
via local controls (irrespective of the selector switch position)
This function uses the same input signal as the <Enabling local controls> function.
Application
No changing possibility via selector switch from LOCAL
Condition
For the <Priority REMOTE> function, a digital input for the signal Enable Local has
to be available and configured.
Configuration of digital input
Required user level: Specialist (4).
Device configuration M0053
I/O interface M0139
Digital inputs M0116
Example
Use input DIN 5 for signal Enable Local:
Parameter: Signal DIN 5 M0122
Setting value: Enable Local (wiring diagram designation: Enable LOCAL)
Information
The logic for the digital inputs may be inverted. Depending on the parameter setting
(e.g. Coding DIN 5 M0127), the input is either High active or Low active. Default
setting is High active.
Priority REMOTE via digital input
Switching behaviour for coding High active:
Input Enable Local = high level (standard: +24 V DC):
Operation via local controls enabled
Input Enable Local = low level (0 V DC or input open):
Priority REMOTE: Operation via local controls disabled
9.5.1. Priority REMOTE: activate
Required user level: Specialist (4) or higher.
81
Actuator controls
ACV 01.2/ACVExC 01.2 Failure functions

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AUMA ACVExC 01.2 Series and is the answer not in the manual?

AUMA ACVExC 01.2 Series Specifications

General IconGeneral
BrandAUMA
ModelACVExC 01.2 Series
CategoryController
LanguageEnglish

Related product manuals