Figure 59: Example of frequency-acceleration histogram
The following further information is saved with the histogram (can be requested via
push button Details).
Starting date: Date of first measurement
Saving date: Date of last measurement
Scaling: Y-axis (acceleration)
14.5. Maintenance (information and signals)
Characteristics
Actuator controls monitor various parameters set in the factory which have an impact
on the wear of the actuator. Once one of these parameters exceeds a determined
limit, the actuator controls generate a signal:
Status indication: S0005 Warnings (AUMA category)
-
Details: Maintenance required
Status indication: S0010 Maintenance required (NAMUR category)
- Details: shows the parameter(s) for which the limit was exceeded, causing
the Maintenance required signal.
Apart from the parameter monitoring preset in the factory (MT lifetime
mechanics/O-rings/lubricant/contactors), a fixed maintenance interval can additionally
be configured, triggering the same signal when exceeding the configured time.
The current maintenance status of the monitored parameters is represented in a bar
chart.
Once maintenance is complete, the parameter initiating maintenance must be reset
to zero.
Application
Maintenance on demand, i.e. the function can be used to perform maintenance
depending on the intensity and load of the actuator.
Activate maintenance signals
Required user level: Specialist (4) or higher.
Device configuration M0053
Application functions M0178
Activation M0212
Maintenance signals M1136
Default value: Function not active
Setting values:
Function not active
<Maintenance signals> function deactivated.
Function active
<Maintenance signals> function activated.
Activate <Maintenance interval> function
Required user level: Specialist (4) or higher.
Device configuration M0053
Application functions M0178
Activation M0212
Maintenance interval M1137
Default value: Function not active
118
Actuator controls
Plant Asset Management ACV 01.2/ACVExC 01.2

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AUMA ACVExC 01.2 Series and is the answer not in the manual?

AUMA ACVExC 01.2 Series Specifications

General IconGeneral
BrandAUMA
ModelACVExC 01.2 Series
CategoryController
LanguageEnglish

Related product manuals