Device configuration M0053
Application functions M0178
Activation M0212
Priority REMOTE M0770
Default value: Function not active
Setting values:
Function not active
<Priority REMOTE> function is deactivated.
Function active
<Priority REMOTE> function is activated.
9.5.2. Priority REMOTE behaviour
This function determines which selector switch functions (LOCAL, OFF) require an
additional enable signal.
Required user level: Specialist (4) or higher.
Customer settings M0041
Local controls M0075
Priority REMOTE M0773
Default value: Sel. sw. Local
Setting values:
Sel. sw. Local
Priority of control from REMOTE is only effective in operation mode LOCAL (selector
switch is in position Local control). If no enable signal is present, operation via push
buttons on the local controls is disabled, the actuator can be controlled from REMOTE
and the controls indicate the symbol in the status line of the display (menu S0001).
Sel. sw. Local + Off
Priority of control from REMOTE is effective in operation modes LOCAL and OFF
(selector switch positions Local control and 0). If no enable signal is present,
operation via push buttons on the local controls is disabled, the actuator can be
controlled from REMOTE and the controls indicate the symbol in the status line
of the display (menu S0001).
9.6. Interlock (enabling operation commands)
Characteristics
●
An operation command will only be executed if an additional enable signal for
the operation command is present.
●
Enabling may be activated or deactivated individually for operation commands
OPEN and CLOSE.
●
Enabling can be set for the different operation modes.
Condition
For the function <Interlock>, a digital input for the signal Enable OPEN has to be
available and configured.Enable CLOSE
Configuration of digital input
Required user level: Specialist (4).
Device configuration M0053
I/O interface M0139
Digital inputs M0116
Example
Use input DIN 5 to enable operation commands in direction CLOSE:
Parameter: Signal DIN 5 M0122
Setting value: Enable CLOSE (wiring diagram designation: Interlock CLOSE)
Information
The logic for the digital inputs may be inverted. Depending on the parameter setting
(e.g. Coding DIN 5 M0127), the input is either High active or Low active. Default
setting is High active.
82
Actuator controls
Failure functions ACV 01.2/ACVExC 01.2