104 Installing the Avaya S8700 Media Server with an Avaya G650 Media Gateway
December 2003
Wiring Block Diagram
Testing These alarms then should be tested using the test eda-external-device-alarm all command as
follows:
# Signal Port Alarm Type
Alt Name
(7 char. limit) Test to bring in alarm.
1 BOD2 01major minor BatChg Remove AC power by turning
off the equipment room breaker
for the GMCC.
2 ACF2 01 minor minor AC Remove AC power by turning
off the equipment room breaker
for the GMCC.
3 BIF2 01C0901 minor BIU Unplug the -48VDC BATT
connector this will cause the
BNA LED to come on and the
BIU to alarm.
4 RFA2 01C0902 minor RECT Unplug rectifiers one at a time
until this alarm comes in
indicating you no longer have
N+1 sparing of rectifiers for
your load.