Configuring the SNMP modules in the uninterruptible power supplies
Installing the Avaya S8700 Media Server with an Avaya G650 Media Gateway 49
December 2003
8 Connect one end of a CAT5 cable to the RJ45 connector on the UPS 1 SNMP module and the
other end to the next available port on the Ethernet switch for Control Network A (CNA).
9 Depending on the reliability configuration to be installed (Duplex reliability configurations on
page 49 or High or critical reliability configurations
on page 49), repeat steps 5 thru 7 for the UPS
2 SNMP module.
10 Connect one end of a CAT5 cable to the RJ45 connector on the UPS 2 SNMP module and the
other end to the next available port on the Ethernet switch for Control Network A (CNA).
Duplex reliability configurations
For duplex reliability configurations, use the following address and cable connection information for
UPS 2:
NOTE:
For duplex reliability configurations there are two servers and two UPS units. However,
there is only one control network. The following entries provide addresses on CNA for
UPS 2.
UPS IP address / Subnet mask = 198.152.255.238 / 255.255.255.0
Default Gateway IP address = 198.152.254.202
Host Table trap receiver IP address = 198.152.254.202
Local network administrator supplied information as required for Get and Set community name
strings.
Cable the RJ45 connector on the UPS 2 SNMP module to the next available port on the Ethernet
switch for Control Network A (CNA).
High or critical reliability configurations
For high and critical configurations, use the following addresses and cable connection information for
UPS 2:
UPS IPaddress / Subnet mask = 198.152.255.239 / 255.255.255.0
Default Gateway IP address = 198.152.255.202
Host Table trap receiver IP address = 198.152.255.202
Local network administrator supplied information as required for Get and Set community name
strings.
Cable the RJ45 connector on the UPS 2 SNMP module to the next available port on the Ethernet
switch for Control Network B (CNB).