Configuring the SNMP modules in the uninterruptible power supplies
Installing the Avaya S8700 Media Server with an Avaya G650 Media Gateway 49
December 2003
8 Connect one end of a CAT5 cable to the RJ45 connector on the UPS 1 SNMP module and the
other end to the next available port on the Ethernet switch for Control Network A (CNA).
9 Depending on the reliability configuration to be installed (Duplex reliability configurations on
page 49 or High or critical reliability configurations
on page 49), repeat steps 5 thru 7 for the UPS
2 SNMP module.
10 Connect one end of a CAT5 cable to the RJ45 connector on the UPS 2 SNMP module and the
other end to the next available port on the Ethernet switch for Control Network A (CNA).
Duplex reliability configurations
For duplex reliability configurations, use the following address and cable connection information for
UPS 2:
NOTE:
For duplex reliability configurations there are two servers and two UPS units. However,
there is only one control network. The following entries provide addresses on CNA for
UPS 2.
• UPS IP address / Subnet mask = 198.152.255.238 / 255.255.255.0
• Default Gateway IP address = 198.152.254.202
• Host Table trap receiver IP address = 198.152.254.202
• Local network administrator supplied information as required for Get and Set community name
strings.
• Cable the RJ45 connector on the UPS 2 SNMP module to the next available port on the Ethernet
switch for Control Network A (CNA).
High or critical reliability configurations
For high and critical configurations, use the following addresses and cable connection information for
UPS 2:
• UPS IPaddress / Subnet mask = 198.152.255.239 / 255.255.255.0
• Default Gateway IP address = 198.152.255.202
• Host Table trap receiver IP address = 198.152.255.202
• Local network administrator supplied information as required for Get and Set community name
strings.
• Cable the RJ45 connector on the UPS 2 SNMP module to the next available port on the Ethernet
switch for Control Network B (CNB).