EasyManua.ls Logo

Avaya S8700 - Page 120

Avaya S8700
298 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
120 Installing the Avaya S8700 Media Server with an Avaya G650 Media Gateway
December 2003
4 At the next (if provided) DC Power media gateway, connect a 6 AWG (#40) (16 4 mm
2
) media
gateway GROUND wire to the media gateway ground terminal block GROUND DISCHARGE
bar.
5 Route the media gateway GROUND wire to first media gateway and connect to the single-point
ground block and connect block.
NOTE:
If a media gateway is located remotely (in a separate room or building), route the media
gateway GROUND wire to an approved protective ground.
6 Repeat connecting each media gateway to the single-point ground block.
7 Connect a 6 AWG (#40) (16 mm
2
) ground wire to an unused terminal on the single-point ground
block.
8 Route the ground wire to the AC load center ground and connect.
Figure 34: Typical MCC1 Media Gateway grounding wiring diagram
Figure notes
1 Media Gateway
2 Media Gateway Ground Terminal
Block
3 6 AWG (#40) (16 mm
2
) Media
Gateway GROUND Wire
4 Single-Point Ground Block
5 6 AWG (#40) (16 4 mm
2
) Ground Wire to
Approved Ground
6 AC Load Center Single-Point Ground
7 Approved Ground
8 Over 50 ft. (15.2 m)
6
1 3
5
widfspg2 KLC 091603
8
4
2
7

Table of Contents

Other manuals for Avaya S8700

Related product manuals