120 Installing the Avaya S8700 Media Server with an Avaya G650 Media Gateway
December 2003
4 At the next (if provided) DC Power media gateway, connect a 6 AWG (#40) (16 4 mm
2
) media
gateway GROUND wire to the media gateway ground terminal block GROUND DISCHARGE
bar.
5 Route the media gateway GROUND wire to first media gateway and connect to the single-point
ground block and connect block.
NOTE:
If a media gateway is located remotely (in a separate room or building), route the media
gateway GROUND wire to an approved protective ground.
6 Repeat connecting each media gateway to the single-point ground block.
7 Connect a 6 AWG (#40) (16 mm
2
) ground wire to an unused terminal on the single-point ground
block.
8 Route the ground wire to the AC load center ground and connect.
Figure 34: Typical MCC1 Media Gateway grounding wiring diagram
Figure notes
1 Media Gateway
2 Media Gateway Ground Terminal
Block
3 6 AWG (#40) (16 mm
2
) Media
Gateway GROUND Wire
4 Single-Point Ground Block
5 6 AWG (#40) (16 4 mm
2
) Ground Wire to
Approved Ground
6 AC Load Center Single-Point Ground
7 Approved Ground
8 Over 50 ft. (15.2 m)
6
1 3
5
widfspg2 KLC 091603
8
4
2
7