98 Installing the Avaya S8700 Media Server with an Avaya G650 Media Gateway
December 2003
Figure 18: Power distribution unit (J58890CH)
Grounding to an AC load center more than 50 feet (15.2 meters)
from media gateway
1 Mount the single-point ground block to any surface between the media gateways and the AC load
center single-point ground. The single-point ground block must be mounted to a non-metallic
surface.
2 At the bottom rear of the first media gateway, connect a 6 AWG (#40) (16 mm
2
) media gateway
GROUND wire to the media gateway ground block. See Figure 19, Typical media gateway
grounding wiring diagram, on page 99.
3 Route the opposite end of the wire to the single-point ground block and connect.
4 At the next media gateway, connect a 6 AWG (#40) (16 4 mm
2
) media gateway GROUND wire to
the media gateway ground block.
NOTE:
If a media gateway is located remotely (in a separate room or building), route the media
gateway GROUND wire to an approved protective ground.
5 Repeat connecting each media gateway to the single-point ground block.
6 Connect a 6 AWG (#40) (16 mm
2
) ground wire to an unused terminal on the single-point ground
block.
7 Route the ground wire to the AC load center ground and connect.
Figure notes
1 Ground Terminal Block 2 To AC load center or approved single-
point ground block
External Alarms
-4
8
V
D
C
R
e
tu
r
n
C
a
rr
ie
r
B
A
C
D
E
F
/G
-48
V
D
C
B
a
tter
ie
s
001c LAO 091103
1
2