Installing the Avaya™ S8700 Media Server with Avaya™ MCC1 or SCC1 Media Gateway
May 2003
NOTE:
The ground plates and cabinet clips are installed later in this procedure.
Connect Ground to DC power cabinet
‘Connect Ground for DC power cabinet’’ on page 104
‘Connect DC Power Distribution Unit Ground’’ on page 105
‘Connect DC Power Cabinet Ground’ on page 106
Connect Ground for DC power cabinet
1 At the DC power cabinet, connect a 1 AWG (#70) (7 mm
2
) ground wire to the GROUND
DISCHARGE bar. See ‘Grounding for DC power cabinet’’ on page 104
.
2 Route the ground wire out of the cabinet and terminate it on the approved ground.
!
CAUTION:
The approved ground must be connected using the correct gauge wire, terminated with a
listed clamp, and identified with a grounding tag (FORM 15657NR, or equivalent).
Grounding for DC power cabinet
Connect DC Battery Frame Ground
1 Cut a length of 6 AWG (#40) (4 mm
2
) wire long enough to reach between the DC power
cabinet and the DC battery cabinet. See ‘Frame Ground Wiring Between cabinet and
Battery Cabinet’’ on page 105.
2 Crimp a terminal lug on the each end of the wire. The terminal lugs are furnished as part
of D-181895, kit of parts.
Figure notes
1 DC power cabinet
2 To Approved Ground
3 1 AWG (#70) (7 mm
2
) Wire
4 Ground Discharge Bar
3
4
1
2
dc_rect1 RBP 051396