79
Installing the Avaya™ S8700 Media Server with Avaya™ MCC1 or SCC1 Media Gateway
May 2003
Power Distribution Unit (J58890CH)
Connect Large Battery Holdover
When using large battery holdover, 1 battery media gateway is required for every S8700
Multi-Connect configuration media gateway requiring holdover. The 24-cell battery media
gateway must have a float voltage of 54.2 VDC.
1 Connect the -48 VDC cable to the large battery connector. See ‘‘Power Distribution Unit
(J58890CH)’’ on page 80.
2 Connect the -48 VDC RETURN cable to the ground terminal block.
3 Connect the temperature sensor cable, from the battery media gateway, to J20.
NOTE:
An adapter cable may be required when connecting the temperature sensor cable to the
J58890CH unit. See ‘‘Temperature Sensor Cable Adapter Cables’’ on page 80
.
Figure notes
1 External Alarm Cable Connector
2 RPO cable
3 Circuit Breakers
4 Pin 6 (-RPO)
5 Pin 2 (+RPO)
6 External Alarm Cable