80
Installing the Avaya™ S8700 Media Server with Avaya™ MCC1 or SCC1 Media Gateway
May 2003
Power Distribution Unit (J58890CH)
Connect Shorting Cable to J58890CE-2
!
CAUTION:
For a media gateway with a battery charger, read the caution label on the 397C battery
charger before disconnecting batteries.
Figure notes
1 Connect small battery holdover cable
(or temperature sensor cable from large
battery media gateway) to J20
2 Carrier Circuit Breakers
3 Ground Terminal Block
4 Connect -48 VDC Return - 1 AWG (50
mm
2
) red cable here
5 Connect -48 VDC - 1 AWG (50 mm
2
)
black cable
6 1 AWG (50 mm
2
) 50 ft. (15.2 m)
cable to large battery media
gateway. For cables greater than 50
ft. (15.2 m), contact your Avaya
representative.
7 Ground Terminal Block
8 To AC load center or approved
single-point ground block
Temperature Sensor Cable Adapter Cables
H600-476 Adapter Cable Usage
Group 1 (G1) 24-cell customer-provided battery
Group 3 (G3) (included
with battery media
gateway)
24-cell Avaya battery
External Alarms