Installing the Avaya™ S8700 Media Server with Avaya™ MCC1 or SCC1 Media Gateway
May 2003
Some media gateways contain a J58890CE-2 AC Power Distribution Unit without an optional
battery charger. Install the shorting cable only when a battery charger is not installed. If you do
not install the shorting cable or a battery charger, then an alarm appears.
1 Set the circuit breakers on the power distribution unit OFF. See ‘Shorting Cable
Installation’’ on page 81.
2 At the rear of the media gateway, insert the shorting cable (H600-442-G1) into J11. The
cable is keyed so it can fit only 1 way.
Shorting Cable Installation
Connect AC Power
1 Set the main circuit breakers on the power distribution unit OFF.
2 Connect media gateway AC line cords to the AC power receptacles.
NOTE:
Do not power up the S8700 Multi-Connect configuration at this time.
Connect DC Power and Ground
!
CAUTION:
Grounding of the S8700 Multi-Connect configuration shall comply with the general rules
for grounding contained in Article 250 of the National Electrical Code, NFPA 70. For
more information, refer to Approved Grounds
.
Figure notes
1 Shorting Cable (H600-442-G1) (if battery
charger is not installed)
2 J11

Table of Contents