Check Commercial Power and Connect AC Power
Before powering up the media gateways, check the AC power using a KS-20599 digital
voltmeter (DVM) (or equivalent).
1 Set the DVM to the 250 volt range.
2 Carefully measure the voltage between the hot and neutral side of the receptacle. The
neutral wire is white, the hot wire is black.
3 Verify the meter reads 106 to 128 VAC. If not, have a qualified electrician correct the
problem.
4 Measure the voltage between the neutral and ground side of the receptacle. The ground
wire is green.
5 Verify the meter reads 0 VAC. If not, have a qualified electrician correct the problem.
6 Set all media gateway power modules OFF. Plug the AC power cable into the receptacle.