106
Installing the Avaya™ S8700 Media Server with Avaya™ MCC1 or SCC1 Media Gateway
May 2003
3 Route the opposite end of the wire to the DC-powered Distribution Unit and connect the
wire to the GRD connector.
4 Repeat Steps 2 and 3 for each remaining DC-powered Distribution Unit.
Ground for the DC-Powered Distribution Unit
Connect DC Power Cabinet Ground
1 Cut a length of 6 AWG (#40) (4 mm
2
) wire long enough to reach between the GROUND
DISCHARGE bar on the DC power cabinet and the single-point ground block on the
expansion control media gateway A (bottom media gateway in ‘Ground for Media
Gateway’’ on page 107).
2 At the DC power cabinet, connect the wire to the GROUND DISCHARGE bar.
3 Route the wire to expansion control media gateway A and connect to the single-point
ground block.
4 Repeat for each expansion control media gateway A in the S8700 Multi-Connect
configuration room.
Figure notes
1 DC power cabinet
2 DC Power Distribution Unit
3 Ground Discharge Bar
4 6 AWG (#40) (4 mm2) Wire
5 GRD Connector Terminal on DC-Powered
Distribution Unit
6 To Additional DC-Powered Distribution Units
(if required)
j58890r1 RBP 042296