Install Sneak Fuse Panels
For general information, see ‘‘Install Sneak Current and Off Premise Protection’’ on page 163
.
The ‘‘Model 507B sneak fuse panel’’ on page 164
, or equivalent, is recommended for sneak
current protection. The panel contains two 25-pair connectors, fuse removal tool, and fifty
220029 sneak fuses (and two spares). See ‘‘Sneak fuse connector pinout’’ on page 165
for
pinout data.
1 Locate the 507B near the network interface or the Main Distribution Frame (MDF).
2 Hold the panel against the mounting surface and mark the mounting screw locations.
Drill pilot holes at the marked locations and partially install a locally obtained #12 x
3/4-inch screw into the two bottom mounting slots.
3 Slide the sneak fuse panel onto the mounting screws and tighten the screws securely.
4 Install a locally obtained #12 x 3/4-inch screw into the top two mounting slots and
tighten securely.
5 Repeat the procedure for each sneak fuse panel.
6 Secure the B25A cable to the panel with the captive screw on the connector and a
supplied cable tie.