105
Installing the Avaya™ S8700 Media Server with Avaya™ MCC1 or SCC1 Media Gateway
May 2003
3 At the DC battery cabinet, attach the 6 AWG (#2540) (6 4 mm
2
) wire to the frame
ground mounting hole using a pan head slotted screw, star washer, and hex nut. Tighten
the screw securely.
4 Route the opposite end of the wire to the DC power cabinet.
5 Attach the 6 AWG (#40) (4 mm
2
) wire to the mounting hole in the top of the cabinet. Use
a pan head slotted screw, star washer, and hex nut. Tighten the screw securely.
Frame Ground Wiring Between cabinet and Battery Cabinet
Connect DC Power Distribution Unit Ground
1
Measure and cut a length of 6 AWG (#40) (4 mm
2
) wire long enough to reach between
the GROUND DISCHARGE bar in the DC power cabinet and the GRD connector on the
DC-powered Distribution Unit. See ‘‘Ground for the DC-Powered Distribution Unit’’ on
page 106.
2 At the cabinet, connect a the 6 AWG (#40) (16 4 mm
2
) wire to the GROUND
DISCHARGE bar.
Figure notes
1 6 AWG (#40) (4mm
2
) Wire
2 DC Battery Cabinet
3 DC power cabinet
4 Grounding Hole in Top of cabinet
5 Terminal Lug (Part of D-18181895)
6 Pan Head Slotted Screw
7 Star Washer
8 Hex Nut
3
1
2
dc