EasyManua.ls Logo

Avaya S8700 - Page 246

Avaya S8700
326 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
246
Installing the Avaya™ S8700 Media Server with Avaya™ MCC1 or SCC1 Media Gateway
Installing and Wiring Telephones
May 2003
5 Make cross-connections for each emergency trunk/emergency station pair.
The 808A is connected to the Main Distribution Frame (MDF) by means of a B25A
cable. ‘Connections for Telephone Used for Emergency Transfer’ on page 249
shows
the connections at the trunk/auxiliary field for a telephone used only for emergency
transfer.
‘Connections for Telephone Used for Emergency Transfer and as Normal Extension’’ on
page 250 shows the connections at the trunk/auxiliary field for a telephone used for
emergency transfer as well as a normal extension.
6 On the trunk identification label at the bottom of the panel, record the trunk line,
extension, and location for each circuit.
7 To each telephone designated as an emergency terminal, attach a label identifying it as
such. The labels are provided with the unit.
8 Check for normal operation as follows:
Place the test switch (switch 12) in NORMAL OPERATION.
Ensure the power supply is providing -48 VDC at 80 mA maximum. The power
LED should be ON.
Check wiring connections.
Verify there is dial tone on all emergency transfer sets.
If all of the above conditions are not met, remove the panel from service and replace it
with a new panel.
9 Check for transfer operation as follows:
Place the test switch (switch 12) in the ACTIVATED position.
The power LED should be OFF.
Verify there is dial tone on all emergency transfer sets.
If all of the above conditions are not met, remove the panel from service and replace it
with a new panel.
.
Trunk/Test Switches
Switch Number Circuit Number
11
2 1
32
4 2
53
6 3
74
8 4

Table of Contents

Other manuals for Avaya S8700

Related product manuals