5 ‘Connect AC Power’’ on page 81
Power Supply Sources (J58890CE-1, J58890CE-2,
and J58890CH-1)
The connect AC power and ground procedures apply to the AC-powered media gateways.
Any of these power sources can supply 60 Hz power to the AC load:
Single-phase, 4-wire, 120/240 VAC supplying 240 VAC.This source has 2 hot wires, 1
ground wire, and 1 neutral wire (J58890CE).
Single-phase, 4-wire, 120/208 VAC supplying 208 VAC. This source has 2 hot wires, 1
ground wire, and 1 neutral wire (J58890CE).
Single-phase, 3-wire, 208 or 240 VAC. This source has 2 hot wires and 1 ground wire
(J58890CH).
Either of these power sources can supply 50 Hz power to the AC load:
Non-US 5-wire, Y, 220/380 VAC. This source has 3 hot wires, 1 neutral wire, and 1
ground wire.
Non-US Delta, 4-wire, 220 or 240 VAC. This source has 3 hot wires and 1 ground wire
(describes the power sources and required AC input power).
s8700 Multi-Connect configuration Power Requirements
Maximum DEFINITY UL Rating Label Power Capacity
Iac InMax W In BTU/Hr.
208 24 3245 11071.26
240 21 3276 11177.71
120 40 3120 10645.44