3-2
TotalAlert Innity™ HTM Medical Gas Notication System
4107 9016 60.01
Figure 3.2: Wiring Diagram for TotalAlert Innity™ Area Alarm
FACTORY WIRED
CHASSIS GROUND
ENCLOSURE
GROUND SCREW
NOTES:
1. MAIN DISCONNECT PROVIDED BY OTHERS
2. FIELD POWER WIRING TO BE COPPER RATED FOR 75°C MINIMUM
3. FIELD SIGNAL WIRING TO BE MINIMUM 22AWG
MULTI-CONDUCTOR CABLE MUST BE TWISTED PAIR TYPE WITH SHIELD.
TOTAL CIRCUIT LENGTH NOT TO EXCEED 100 METERS.
4. SIGNAL INPUTS (UP TO 8) FROM GAS SENSOR MODULES.
5. RELAY OUTPUT CONTACT RATED 3A / 30VDC MAX.
6. SEE MODULE LABEL TO SET MODULE ADDRESS (POSITIONS 2, 3 & 4)
7. SET ADDRESS SWT POSITION 1 TO “ON” FOR LAST MODULE IN CHAIN ONLY.
3.2 HTM Area Wiring Diagram