EasyManua.ls Logo

BeaconMedaes TotalAlert Infinity - Medipoint and Shire Network Configuration; Medipoint Network Setup

BeaconMedaes TotalAlert Infinity
122 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-43
TotalAlert Innity™ HTM Medical Gas Notication System
4107 9016 60.01
Figure 151: Signal Settings Screen
Figure 152: Signal Settings Screen
To congure the remaining signal settings, repeat
the above steps.
Touch the Save button when you see a check
beside your selection to save the selection and
return to the SIGNAL SETTINGS screen.
4.8 Medipoint/Shire Network
4.8.1 Medipoint Network
The Medipoint alarm system works by identifying each
individual gas channel or set or point alarm inputs with
a unique ID. The switches are hexadecimal (i.e. A corre-
sponds to 10, B corresponds to 11 etc. for the purposes
of panel identication. A channel must be set between
0 and F, 0 being OFF.
The panel with the highest ID must be set as the MAS-
TER panel, all other panels must be set as slave panels.
Therefore an alarm system may contain up to 32 pan-
els with the highest number being set as the MASTER.
An alarm system is set up by allocating a number (1 to
9) or letter (A to F) to each set of plant inputs or point
alarm inputs. Typically on a 4 gas system with point
alarms:
1 - Oxygen Manifold Alarms
2 - Nitrous Oxide Manifold Alarms
3 - Air Plant Alarms
4 - Vacuum Plant Alarms
A - Ward 1 to 4 Point Alarms
B - Ward 5 to 8 Point Alarms
Therefore on every panel where Oxygen is to be dis-
played the appropriate gas number is set to 1.
4.8.2 Medipoint Network Setup
Go to the PRIMARY SETTINGS tab (from the congura-
tion screen) to setup the HTM SETTINGS for the Medi-
point Network. (See Figure 4.153)
Figure 153: Medipoint Network Setup

Table of Contents

Other manuals for BeaconMedaes TotalAlert Infinity

Related product manuals