3-1
TotalAlert Innity™ HTM Medical Gas Notication System
4107 9016 60.01
Figure 3.1: Wiring Diagram for TotalAlert Innity™ Central Alarm
FACTORY WIRED
CHASSIS GROUND
3.0 Wiring Schematics
3.1 HTM Central Wiring Diagram
NOTES:
1. MAIN DISCONNECT PROVIDED BY OTHERS
2. FIELD POWER WIRING TO BE COPPER RATED FOR 75°C MINIMUM
3. FIELD SIGNAL WIRING TO BE MINIMUM 22AWG
MULTI-CONDUCTOR CABLE MUST BE TWISTED PAIR TYPE WITH SHIELD
TOTAL CIRCUIT LENGTH NOT TO EXCEED 100 METERS
4. MEDIPOINT & SHIRE WIRING TO BE MINIMUM 24 AWG.
MULTI-CONDUCTOR CABLE MUST BE TWISTED PAIR TYPE WITH SHIELD.
TOTAL CIRCUIT LENGTH NOT TO EXCEED 1200 METERS.
5. SIGNAL INPUTS FROM BEACONMEDAES LINE CONTACT MONITORING
CONTACTS.
6. RELAY OUTPUT CONTACT RATED 3A / 30VDC MAX.
7. SEE MODULE LABEL TO SET MODULE ADDRESS (POSITIONS 2, 3 & 4)
8. SET ADDRESS SWT POSITION 1 TO “ON” FOR LAST MODULE IN CHAIN ONLY.
ENCLOSURE
GROUND
SCREW