Error correction
EL72x1174 Version: 3.3
Text ID Type Place Text Message Additional comment
0x4414 Warning Drive I2T-Model Motor over-
load (Warning)
- The motor is being operated outside the parameter-
ized rated values
- The I2T-model of the motor is incorrectly parameter-
ized
0x4415 Warning Drive Speed limitation active The maximum speed is limited by the parameterized
objects (e.g. velocity limitation, motor speed limitation).
This warning is output if the set velocity is higher than
one of the parameterized limits
0x4416 Warning Drive Step lost detected at po-
sition: 0x%X%X
Step loss detected
0x4417 Warning Drive Motor overtemperature The internal temperature of the motor exceeds the pa-
rameterized warning threshold
0x4418 Warning Drive Limit: Current Limit: current is limited
0x4419 Warning Drive Limit: Amplifier I2T-
model exceeds 100%%
The threshold values for the maximum current were
exceeded.
0x441A Warning Drive Limit: Motor I2T-model
exceeds 100%%
Limit: Motor I2T-model exceeds 100%
0x441B Warning Drive Limit: Velocity limitation The threshold values for the maximum speed were ex-
ceeded.
0x441C Warning Drive STO while the axis was
enabled
An attempt was made to activate the axis, despite the
fact that no voltage is present at the STO input.
0x4600 Warning General IO Wrong supply voltage
range
Supply voltage not in the correct range
0x4610 Warning General IO Wrong output voltage
range
Output voltage not in the correct range
0x4705 Warning Processor usage at %d
%%
Processor load at %d %%
0x470A Warning EtherCAT Frame missed
(change Settings or DC
Operation Mode or
Sync0 Shift Time)
EtherCAT frame missed (change DC Operation Mode
or Sync0 Shift Time under Settings)