6.5 Operating behavior in the case of bus connection failure
The operating behavior in the case of failure of the PROFINET systems can be param-
eterized. The required behavior can be set via parameter Bus Error behavior 388.
Operating point is maintained.
1
Error
“Fault” status will be activated immediately. Factory
setting.
2
Stop
Control command “Disable voltage” and switch to
“switch on disabled” status.
3
Quick stop
Control command “Quick stop” and switch to “switch
on disabled” status.
4
Shutdown + Error
Control command “Disable operation” and switch to
“Error” status once the drive has been shut down.
5
Quick stop + Error
Control command “Quick stop” and switch to “Error”
status once the drive has been shut down.
The parameter settings Bus Error Behaviour 388
= 2…5 are evaluated depending
on parameter Local/Remote 412.
There are numerous options of parameterizing the fault and warning behavior of the
frequency inverter. For details about possible faults, refer to Chapter 13.5 “Error me
10/13 CM-PROFINET 25