11.4.1.1 Sequence example
In order to start “velocity mode”, the correct sequence must be sent by the PLC.
Set Acceleration (clockwise) 420 to the required value
(factory setting: 5 Hz/s)
Set
Deceleration (clockwise) 421 to the required value
(factory setting: -0.01 Hz/s)
→ -0.01 means that the value set for the acceleration will also be used for dece
OUT
IN
Control word
Status word
Modes of operation
Mod. Of. Op. Displ.
Reference
actual
Remark
Enable operation, no change of pre-
vious status if already enabled.
Starts “Velocity mode” with reference
value from OUT-PZD12
r)
1299 S. Special Function Generator:
= “9-Zero”
Starts “Velocity mode” with ref-
erence value from OUT-PZD12
r)
0xABCD.
1299 S. Special Function Generator
≠ “9-Zero”
Starts with reference value with
source from 1299
S. Special
Starts “Velocity mode” with reference
value “0”
1299 S. Special Function Generator:
= “9-Zero”
Starts “Velocity mode” with ref-
erence value “0”
1299 S. Special Function Generator
≠ “9-Zero”
Starts with reference value with
source from 1299
S. Special
Starts “Velocity mode” at current
speed – current ramps will be can-
10/13 CM-PROFINET 81