8.4 Frequency conversion PDP-Word to internal representation
If the frequency inverter is equipped with a PROFINET module CM-PROFINET or an
extension module with Systembus, the
Convert PDP/internal
function will be availa-
ble
.
It converts frequency values with Profibus representation to frequency values
with device-internal representation and vice versa, see Chapter
11.3.3Reference
value/actual value”.
Frequency conversion Profibus representation/ Internal representation
The standardization for In-F-PDP-word1/2 and Out-F-PDPconv-word1/2 is:
Standardization
Reference
Value
Binary
Decimal
Hexadecimal
+ 100%
+ 2
14
16384
0x4000
- 100%
- 2
14
49152
0xC000
Possible range = ±200% = +32768 to -32768 = 0x7FFF through 0x8000
The function uses its own reference value Convert Reference 1374 for data con-
version. The advantage of this function is the fact that the “Word” data type is used
for frequency values instead of the “Long” data type.
10/13 CM-PROFINET 47