Solution 16i
Installation Manual Comms Programming
Comms > Dialler Reporting > L547
Fire Report Delay
MENU 5-4-7
0 0 0
(*** System Wide Parameter ***)
SECONDS
This menu programs how long the panel will delay
reporting re zone alarm reports. Only re zones that
have been programmed for Delay Report in MENU 3-1-7
— Report Option will follow the Fire Report Delay time.
1) Enter your Installer PIN + [MENU].
2) Enter [5] + [4] + [7] + [OK]. The keypad will display
the current re report delay time.
d= 000
3) Using the numeric keys, enter the new report delay
time then press [OK] to save and exit or press
[MENU] to exit without saving. Valid entires are 0
to 255 seconds.
CO MM S R E GI ST R AT I ON
Comms > MyAlarm >
L550
MyAlarm IP Address
MENU 5-5-0
1 Digits 12
0 0 0 0 0 0 0 0 0 0 0 0
This menu programs the 12 digit MyAlarm IP Address.
i
Note
MENU 5-5-0 should be left at the factory default
settings unless you are advised otherwise by the
manufacturer.
1) Enter your Installer PIN + [MENU].
2) Enter [5] + [5] + [0] + [OK]. The keypad will display
the rst six digits of the MyAlarm server IP address.
000000
3) Use the numeric keys [0] to [9] + [] and [] keys
to program the new MyAlarm IP Address, then
press [OK] to save and exit or press [MENU] to exit
without saving.
Comms > MyAlarm >
L551
MyAlarm Port
MENU 5-5-1
0 7 7 0 1
This menu programs the 5 digit MyAlarm Port number.
Range must be programmed within 0 to 65535.
i
Note
MENU 5-5-1 should be left at the factory default
settings unless you are advised otherwise by the
manufacturer.
1) Enter your Installer PIN + [MENU].
2) Enter [5] + [5] + [1] + [OK]. The keypad will display
the current MyAlarm Port number.
07701
3) Use the numeric keys [0] to [9] + [] and [] keys
to program the new MyAlarm Port number, then
press [OK] to save and exit or press [MENU] to exit
without saving.
Comms > MyAlarm > L552
MyAlarm Options
MENU 5-5-2
1 Reserved N
2 Reserved N
3 Reserved N
4 Reserved N
5 Reserved N
6 Reserved N
7 Reserved N
8 Reserved N
This MENU is currently not used.