8-9
Bosch Security Systems 09/11 BLCC500I
Solution 16i
Installation Manual Output Programming
T IM ED O UT PU TS
Outputs > Properties > L414
Time Parameter
MENU 4-1-4
0 0 0 0 0 0 0 0 0 0 0 0
Hour Minute Seconds 10
th
Sec
The time base parameter is only applicable for output
types that are programmed as one shot or pulsing.
Program 0 to 255 for each of the units (Hour, Minute,
Seconds and 10th of a Second) for the time parameter. If
required, add the units together to give the total one shot
time or pulsing on/o time.
1) Enter your Installer PIN + [MENU].
2) Enter [4] + [1] + [4] + [OK], then select the output
you want to program and press [OK].
3) Using the numeric keys, enter the length of time in
hours, minutes, seconds and 10th of seconds as
required. You can use the left and right arrow keys
to move between screens if no data change is
required.
hh=000
Enter the number of hours (000 to 255).
mm=005
Enter the number of minutes (000 to 255).
ss=000
Enter the number of seconds (000 to 255).
tt=000
Enter the number of 10th seconds (000 to 255).
4) Press [OK] to save and exit or press [MENU] to exit
without saving.
One Shot Mode
The time base is the length of time that the output will
operate. For Example you may want a strobe output
to operate for 1 hour, Either of the examples below will
achieve the 1 hour time.
Total Time Hour Minute Seconds
10th
Sec
60 Minutes 001 000 000 000
60 Minutes 000 060 000 000
Table 29: Example - Output One Shot Timer
Pulsing Mode
The time base is the unit of time that the output will pulse
on and o. If the time base is programmed for 60 seconds,
the output will pulse on for 60 seconds and then o for 60
seconds (repeat) until the output is reset.
Outputs > Properties > L415
Output Options
MENU 4-1-5
1 Do Not Operate On Low Battery Y
2 Display Overload Y
3 Report Overload Y
4 Display Device Fail Y
5 Report Device Fail Y
6 Alarm On Device Fail N
7 Block If Armed All On N
8 Display Output Status On Keypad N
1) Enter your Installer PIN + [MENU].
2) Enter [4] + [1] + [5] + [OK], then enter the output
number you want to program and press [OK].
3) Use the numeric keys [1] to [8] to toggle in or o the
option required.
-Bit-
1 2 3 4 5
4) Repeat Step 3 until all options are programmed as
required, then press [OK] to save and exit or press
[MENU] to exit without saving.
Do Not Operate Output On Low Battery
This option forces the control panel not to operate the
output when a low battery or missing battery condition
is in eect. Once the low battery condition restores, the
output will return to normal operation.
Display Output Overload
This option allows the keypad to display a trouble
condition when output current exceeds its maximum
limit.
Report Output Overload
This option allows the panel to send an Output Overload
report when the output current exceeds its maximum
limit. A restore report will be sent when the current
overload condition no longer exists.