7-2
Bosch Security Systems 09/11 BLCC500I
Solution 16i
Installation Manual Input Programming
Inputs > Commands > L301
Zone Array
MENU 3-0-1
This menu allows you to view zones in groups of four. The
keypad displays the zone status as follows:
n= NORMAL
S = SHORTED
A= ALARM
T= TAMPER
- = DISABLED
1) Enter your Installer PIN + [MENU].
2) Enter [3] + [0] + [1] and use the up and down arrows
to select the zone group to view.
3) The keypad will display the following zone array
information for Zones 1 to 4.
01nSAT
In the above example screen,
N = Zone 01 is Normal (Sealed)
S = Zone 02 is Shorted
A = Zone 03 is in Alarm (Unsealed)
T = Zone 04 is in Tamper Alarm (Unsealed)
4) When nished press [OK] or [MENU] to exit.
Inputs > Commands > bYpAss
Bypass Zones
-
-
MENU 3-0-2
This menu allows you to bypass one or more zones before
you turn an area All On, Part On or Part 2 On. When a zone
is bypassed, it is not able to detect intrusion or sound an
alarm. All non bypassed zones will continue to operate as
normal.
Any zone that has been bypassed will automatically be
un-bypassed when you turn the corresponding area o.
1) Enter your PIN + [MENU].
2) Enter [3] + [0] + [2] + [OK].
The keypad will ash the Zn= prompt. Any zone(s)
which are currently bypassed will also be ashing.
If your system is programmed for multiple areas, the
area icon will also be displayed.
Zn=
1
3 4
I NP UT CO MM AN DS
Inputs > Commands > StAtUS
Zone Status
-
-
-
MENU 3-0-0
his menu allows you to view the status or condition of
each zone on the system. There are four possible states
which can be displayed, Zone Normal, Zone Open, Zone
Tamper and Zone Shorted. The status display will also
show the resistance accross the zone loop.
1) Enter your PIN + [MENU].
2) Enter [3] + [0] + [0] + [OK].
The keypad will display the Zn = prompt.
Zn=
3) Enter the zone number you want to view the status
of, then press [OK].
The keypad will scroll the zone status information.
The rst screen will display the zone state.
There are 4 possible states;
Normal - Zone is closed and ready.
Short - Zone is shorted and not ready.
Open - Zone is open and not ready.
Tamper - Zone tamper circuit is open.
NORMAL
The keypad will now display the zone resistance in
ohms. This resistance is measured by the control
panel.
03198
4) Press the [OK] key to exit.