Page 11 of 113
1.3.1
Flexible Configuration of Program
There are up to 32 segments can be defined for a profile. Each segment can be configured
as a ramp or a dwell (soak) segment or defining a repeat number of cycles at arbitrary location
within the profile and finally terminated by an end segment. The user can edit a currently running
profile.
1.3.2
Maximum Capacity of Program
There are at most 50 Profiles can be defined and 1000 segments totally available for all
profiles. Each Profile can contain maximum of 32 Segments and limited to 1000 Segments in Total.
1.3.3
Event Input
The Event input feature allows the user to select one of eight functions below.
Enter Profile Run Mode
Enter Profile Hold Mode
Abort Profile Mode
Enter Manual Mode
Perform Failure Transfer
Enter Off Mode
Advance to the next segment
Select second set of PID values
1.3.4
Programmable Event Outputs
Up to 3 Relays are configurable for event outputs and the state of each output can be
defined for each segment and end of profile.
1.3.5
High Accuracy
This Process Control Card is manufactured with custom designed ASIC(Application
Specific Integrated Circuit ) technology which contains a 18-bit A to D converter for high resolution
measurement ( true 0.1 F resolution for thermocouple and PT100 ) and a 15-bit D to A converter for
linear current or voltage control output. The ASIC technology provides improved operating
performance with low cost and enhanced reliability and higher density.
1.3.6
Fast Sampling Rate
The sampling rate of the input A to D converter reaches 5 times/second (200msec). The
fast sampling rate allows this Process Control Card to control fast processes.