4.4.6 TEACH-IN PROCEDURES
The Teach-In function identifies and fixes the relationship between the transmitter
display and the real distance, level or volume to ensure accurate measurement.
The transmitter automatically selects the appropriate Teach-In procedure
(distance, level or volume) depending on the configuration and units
selected within the engineering units function - section 4.4.2
● For the Teach-In procedures it is advisable to select either filter 0 or 3
(depending on echo filtering) during the Teach-In procedure for quick
calculation of the measure and after select the desired filter.
● If volume has been selected for measurement and gas
characteristics have to be defined, follow the procedures below:
● Select distance or level with appropriate units within the engineering
units.
● Complete a 2 point Teach-In for identification of the gas characteristics
and ‘END‘ the menu to save the parameters.
● Return to the engineering units and select volume and the appropriate
units.
● Complete a volume Teach-In to fix the transmitter display and the real
distance, level or volume measurement.
4.4.6.1 TEACH-IN FOR LEVEL AND DISTANCE
This function allows the relationship between the transmitter and fluid to be defined by
distance or level.
● For distance measurement it is not necessary to complete a Teach-In
procedure although for accurate measurement it is advised to complete
at least a 1 point Teach-In.
● If the transmitter has been configured as level, it is necessary to
complete at least a 1 point Teach-In.
CURRENT
1 or 2 point Level or
distance Teach-In
procedure
No Teach-In chosen
and advance to the
next option.
Reset the distance
reference point
(Reset is not displayed if configured as level)