SPECIFICATIONS
6.1 SPECIFICATIONS
Specifications in relation to the process
Measurement
Measurement type Level, distance or volume measurement
Measurement range 0.30 to 10 meters compact version and
0.30 to 7 meters wall and panel versions
Measurement range in the
following conditions: Measure of the fluid without foam,
T
ambient
= 20°C ; T
fluid
= 20°C
Ambient pressure value : atmopheric pressure
Accuracy +/- 0.25% of the full scale
+/- 0.15% after calibration with Teach-In
Resolution +/- 3mm
Full beam width 8 degrees conical
Pulse rate 8 pulses per second
Blocking distance 30 cm from the base of the sensor
Installation
Pressure rating 2 bar at 25°C maximum
Mounting threads 2“ G or 2“ NPT
Fluid temperature -40 to +80°C / -40 to +176°F
Gasket material FPM or EPDM (option)
Specifications in relation to the control outputs
Electrical connection
Power supply 18-32VDC
115/230 VAC 50-60Hz (+/- 10% VAC only)
Consumption 200mA maximum
Proportional ouput
Output type Current output of 4-20mA (22mA error signal)
Accuracy + / - 2%
Wiring Sinking or sourcing
Maximum load 1300 Ohms at 32V
1000 Ohms at 24V
550 Ohms at 18V
Output calibration 4-20mA or inverted to 20-4mA adjustable
Relay ouput
Output type 2 relays (3A), normally open
Load DC : 250V, 3A
AC : 250V, 3A
Life expectancy 100 000 cycles (minimum)
Thresholds Hysteresis and delay programmable according to
the level, distance, volume or temperature.