56
8175
ENGLISH
SPECIFICATIONS
Specifications in relation to the user
User‘s interface
Display 8 digits alphanumeric LCD 9mm high
Display :
Current output Generated current indication : xx.xx mA
Relay state Red LEDs on when contact is closed
Programming Menus with 3 programming keys
Protection Lockable switch for the Enter key
Processing
Assistance for commissioning Simulation of the level or volume to check correct
running of the installation
Filtering of the measure 10 levels of filtering (filter 0...9)
Temperature adjustment Programmable depending on the gas medium
Specifications in relation to the environment
Ambient conditions
Storing temperature -20 to +60°C / -4 to +140°F
-40 to +80°C / -40 to +176°F (for the remote sensor)
Humidity Maximum of 80%
Operating temperature -20 to +60°C / -4 to +140°F
-40 to +80°C / -40 to +176°F (for the remote sensor)
Humidity Maximum of 80%
Enclosure rating IP65 (Compact, Wall & Panel front)
IP20 (Interior of panel version)
Enclosure sensor rating IP67
Construction
Dimensions maximum See section 6.3
Weight 1kg maximum
Materials in contact with the environment
Electronic housing PC (20% glass reinforced fiber)
ABS (Wall version)
Transducer material PVDF /POM
Front plate Polyester
Conformity to standards
Emission According to generic norm EN 50081.1
Immunity According to generic norm EN 50082.2
It is important to note that in case of disturbance of the
40-80MHz provided by the cables, the output current
may deviate and drop by 10%.
Safety According to safety regulations for measuring instruments
for regulation and laboratory NF EN 61010-1