74 - 8630
OPERATION AND CONTROLLER FUNCTIONS
SAFEPOS
Entering the safety position
Factory setting: 0 %
SAFEPOS
SPOS XXX
Enter
safety position (0 ... 100 %)
*
With the fast pressurize / fast vent variant, two valves are driven in each case to obtain faster
pressurizing and venting.
*
When the safety position is 0 % or 100 %, the actuator will be
fully
vented or pressurized as soon as the safety position is
activated int he supplementary function
SIG-ERR
or
BIN-IN
.
The safety position set is only moved to when a corresponding signal is present at the
binary input (for configuration see
BIN-IN
), or on occurrence of a signal error (for
configuration see
SIG-ERR
).
This function is executed only in the AUTOMATIC mode.
ATTENTION!