What is the TV-VAVB3-E2?
TruVu™ VAVB3-E2 CARRIER CORPORATION ©2022
Installation and Start-up Guide All rights reserved
4
The TV-VAVB3-E2 also has the following ports:
• Rnet port for connecting ZS sensors, an Equipment Touch, an TruVu™ ET Display, and Wireless Adapter for
wireless sensors
• Comm/Service USB ports for connecting locally to controller setup pages, the TruVu™ ET Display, or the
Carrier wireless service adapter
• Act Net port supports a combination of up to 5 Act Net addresses. Act Net devices must be addressed as
follows:
○ Address 1 is reserved for the built-in actuator
○ Address 2 and 3 are reserved for the VAV Zone II Secondary Duct
○ Address 4 and 5 for s
Specifications
drv_fwex_< version >.driverx
Maximum number of control programs*
2
NOTE You can run 1 VAV Product Integrated Control (PIC)
and 1 programmable Zone Controller II program, OR up to
2 Zone Controller II programs.
Maximum number of BACnet objects*
Third-party BACnet integration points
NOTE Must be on the BACnet/IP network
* Depends on available memory.
24 Vac ±15%, 50–60 Hz, 50 VA
24 Vdc ±10%, 18 W
NOTE The above power consumption is for the controller only. Adding devices to
the Act Net bus increases total power consumed.
Belimo brushless DC motor, torque 45 inch-pounds (5 Nm), runtime 154 seconds
10/100 BaseT, full duplex, Ethernet ports for BACnet/IP and/or BACnet/Ethernet
communication.
Under normal operation, network traffic not destined for this controller is repeated
to the other Ethernet port. When the controller is powered off, all traffic received on
one port is mirrored to the other port.