Appendix A: TV-VAVB3-E2 Points/Properties
TruVu™ VAVB3-E2 CARRIER CORPORATION ©2022
Installation and Start-up Guide All rights reserved
133
Linkage
Navigation:
i-Vu® / Field Assistant:
Properties > Control Program > Linkage
Point Name/Description
Default/Range
Airside Linkage
Click Linkage Collector/Linkage Provider to access the microblock popup's Summary
and Details tabs. See the microblock popup's Help for more detailed explanations.
Linkage Collector For a VAV Master, set the Number of Providers to the total number
of controllers that will report to the Master, including the Master. For a slave, the
Number of Providers is 1. See Linkage (page 68) for additional information.
D:
R:
1
1 to 64
Linkage Provider Depends on this controller's function.
If the controller is...
Enter the MS/TP network number
and MAC address of...
The main VAV Master
The linked air source controller
A sub-master
The main VAV Master
A slave that is not on the same
MS/TP network as its master
Its masters
Network Number
Address
NOTE If you change the Network Number or Address, you must use the i-Vu®
application or Field Assistant to cycle power to the controller for the changes to take
effect.
D:
R:
D:
R:
0
0 to 65,535
0
0 to 127
Airside Linkage Status If Active, the controller is part of a linked system. If Not Active,
the controller is a stand-alone device.
R:
Not Active/Active
Linkage Zone Type Select whether the controller is a Master or a slave.
Select VAV Master if the controller is the Master or a sub-master in a VAV application.
Select VVT Master only if the controller is the Master in a VVT application. VVT
applications do not support sub-masters.
D:
R:
Slave
Slave
VVT Master
VAV Master
Inhibit Heating Call from this zone? - VVT system only. If Yes, the VVT Master ignores
this controller as a heating caller.
D:
R:
No
No/Yes
Active Heating Caller? VVT system only. Determines if the zone will be counted as a
heat caller for system heating when the zone has a local demand for heat.
D:
R:
Yes
No/Yes
Inhibit Cooling Call from this zone? - VVT system only. If Yes, the VVT Master ignores
this controller as a cooling caller.
D:
R:
No
No/Yes