Linkage
Properties > Control Program > Linkage
Click Linkage Collector/Linkage Provider to access the microblock popup's Summary
and Details tabs. See the microblock popup's Help for more detailed explanations.
Linkage Collector – For a VAV Master, set the Number of Providers to the total number
of controllers that will report to the Master, including the Master. For a slave, the
Number of Providers is 1. See Linkage (page 68) for additional information.
Linkage Provider – Depends on this controller's function.
Enter the MS/TP network number
and MAC address of...
The linked air source controller
A slave that is not on the same
MS/TP network as its master
Network Number
Address
NOTE If you change the Network Number or Address, you must use the i-Vu®
application or Field Assistant to cycle power to the controller for the changes to take
effect.
Airside Linkage Status – If Active, the controller is part of a linked system. If Not Active,
the controller is a stand-alone device.
Linkage Zone Type – Select whether the controller is a Master or a slave.
Select VAV Master if the controller is the Master or a sub-master in a VAV application.
Select VVT Master only if the controller is the Master in a VVT application. VVT
applications do not support sub-masters.
Slave
Slave
VVT Master
VAV Master
Inhibit Heating Call from this zone? - VVT system only. If Yes, the VVT Master ignores
this controller as a heating caller.
Active Heating Caller? – VVT system only. Determines if the zone will be counted as a
heat caller for system heating when the zone has a local demand for heat.
Inhibit Cooling Call from this zone? - VVT system only. If Yes, the VVT Master ignores
this controller as a cooling caller.