Appendix A: TV-VAVB3-E2 Points/Properties
TruVu™ VAVB3-E2 CARRIER CORPORATION ©2022
Installation and Start-up Guide All rights reserved
135
I/O Points
WARNINGS
• Do not change the Value, Offset/Polarity, Exp:Num, I/O Type, Sensor/Actuator Type, Min/Max, or Resolution I/O
configuration parameter for the points listed below. Changing these parameters could cause improper control and/or
equipment damage.
• Use extreme caution if locking a point as this may also cause improper control and/or equipment damage.
SPT Sensor/Zone Temp
SPT Sensor - (For the SPT Standard, SPT Plus, and SPT Pro sensors only). Sensor
configurations on the microblock's Properties > Details tab are listed below. For more
information, see the Carrier Sensors Installation Guide.
-56 to 245°F
(-48.9 to 118.3°C)
Do not adjust the following settings:
Min Present Value - Minimum present value the sensor transmits before indicating
an alarm.
Max Present Value - Maximum present value the sensor transmits before
indicating an alarm.
Setpoint Adjustment:
Max Adjust – The amount that a user may adjust the setpoint at the sensors.
5 °F (2.7 °C)
0 to 15 °F
(0 to 8.3 °C)
Reset setpoint adjust to zero when unoccupied - Resets the setpoint bias to zero
when the controller transitions to unoccupied..
Timed Local Override:
Allow Continuous (SPT Pro only) – If checked, a user can press the sensor's local
override button until the Max Accum value is reached, then press one more time
to have a continuous override until the next occupied period or until the user
cancels the override. The display shows On during a continuous override.
Each Pulse – The amount of time added to the total override time when a user
pushes the sensor's override button.
30:00 mm:ss
0:00 to 1440:00 mm:ss
Max Accum – The maximum amount of override time accumulated when a user
pushes the sensor's override button.
240:00 mm:ss
0:00 to 2000:00 mm:ss
Cancel override – How long a user must push the sensor's override button to
cancel an override.
3 seconds
0 to 60 seconds