Appendix A: TV-VAVB3-E2 Points/Properties
TruVu™ VAVB3-E2 CARRIER CORPORATION ©2022
Installation and Start-up Guide All rights reserved
120
Point Name/Description
Default/Range
Space High Humidity Alarm If set to display, shows the alarm indicator on the
communicating zone sensors with display, if the Space Relative Humidity alarm is
active.
D:
R:
Ignore
Ignore/Display
Space High CO2 Alarm If set to display, shows the alarm indicator on the
communicating zone sensors with display if the Indoor Air Quality Alarm is in alarm.
D:
R:
Ignore
Ignore/Display
Maintenance Displayed on ZS Sensor
Linkage Fault If set to display, shows the maintenance indicator on the ZS Pro sensor
if the Airside Linkage is in a Fault condition.
D:
R:
Ignore
Ignore/Display
Net OAT Fault If set to display, shows the maintenance indicator on the ZS Pro sensor
if the Network Outside Air is not valid.
D:
R:
Ignore
Ignore/Display
SPT Sensor Fault If set to display, shows the maintenance indicator on the ZS Pro
sensor if the space temperature sensor is not valid.
D:
R:
Ignore
Ignore/Display
Service Configuration
Navigation:
i-Vu® / Field Assistant:
Properties > Control Program > Configuration > Service Configuration
Point Name/Description
Default/Range
Terminal Type The type of zone terminal that the controller is installed on.
D:
R:
Single Duct
Single Duct
Parallel
Series Fan
Terminal Size Shows the value entered as the Cooling Max Airflow in the Flow Control
object.
D:
R:
2100 cfm
(991.2 liters/second)
0 to 99999 cfm
(liters/second)
Terminal Fan Airflow Enter the terminal fan airflow in cfm (liters/second). Used in
performance calculations only. Available only on fan-enabled terminal box.
D:
R:
1000 cfm
(472 liters/second)
0 to 99999 cfm
(liters/second)
Disable Series Fan When set to Enable, the controller disables the fan on a series-
type terminal when the airflow setpoint equals 0. (We do not recommend configuring
the minimum occupied airflow setpoint to 0, as this does not meet minimum ventilation
requirements.)
D:
R:
N/A
N/A
Enable